Installation Manual
Components
Airscape Air Handler Unit
location piping to the ahu from the pod must be < 100 ft in equivalent length, with < 35 ft of lift configuration & dimensions the airscape air handler units come in three configurations; a, b, and c all configurations require an additional merv 13 filter module, and an a/c economizer/night cooling damper can be added to all configurations the ahu can be pulled apart into individual modules to make it easier to move the unit into a crawl space or attic ensure duct transitions to and from the ahu are adequate for proper, even air flow the ahu can be installed vertically or horizontally warning hydronic coil and a/c coil must be installed downstream of air filters, or the performance will be heavily degraded power the airscape ahu will require a 120v power outlet, which will power the blower motor and provide 24vac power for the thermostat a standard residential gfci plug will trip when the motor starts up use a hardwired switch with fuse, or a heavy duty industrial gfci such as the hubbell wiring device kellems gfsg8200i plumbing connections a frame coil connections should be plumbed in parallel , not series warning failure to plumb coil in regard to orientation to airflow can significantly degrade performance possible piping configurations for the a frame coil