Installation Manual
Components
Tank
warning installation instructions in this manual are not meant to encompass 100% of sanc02 installation guidelines and requirements refer to the manufacturer for complete instructions location the tank can be located no further than 66ft (20m) from the sanco2 heat pump , and no more than 27ft (7m) below it tank must be installed in an area not subjected directly to outside weather dimensions dimension 83 gal 119 gal a height 68 7/8" 63 3/8" b hot water outlet and prv 60 1/4" 56" c heat pump return 60 1/4" 60 1/4" d sensor port 40 5/8" 56" e hydronic return & cold water to hp 8 3/4" 4" f diameter 24 1/2" 28" dry weight 115 lbs note allow space between the tank and the wall for tank insulation to be added later mounting the tank is a passive storage vessel (no internal heating element) therefore, there is no required pedestal flue, or condensing section note min 1" high density insulation below the tank is required (see insulation docid\ tsxlrk3nwwa6e1rl4insr section) for good system performance note it is required to wrap r6, or greater, insulation (see insulation docid\ tsxlrk3nwwa6e1rl4insr section) around the tank it is easiest to do this prior to plumbing it warning follow all local jurisdiction codes for bracing of tank plumbing connections 83 gal 119 gal f air handler return 3/4" npt 1 1/2" npt g hot water outlet 3/4" npt 1 1/2" npt hph hot water return from hp 3/4" npt 3/4" npt h cold water inlet/return to heat pump 3/4" npt 3/4" npt prv pressure relief valve valve provided valve provided note dielectric unions or 6" brass couplings are required at all 119 gal tank connections heat traps (see plumbing system diagrams docid 4gt0qthbwj20pdz9gvbsf ) required for top connections