Harvest Pod
The Pod is required to be installed in weather-protected space at a minimum, such as a garage, basement, crawlspace, indoor closet, or outdoor closet where there is no risk of freezing.
WARNING: The Pod is not intended to be fully waterproof. Install in dry location and take care while modifying plumbing near Pod so as not to damage the Pod's electrical components with water.
WARNING: Always put Pod cover on when soldering to avoid solder splatter on electronic components
Recommended to be installed as close to tank as reasonable, and can be:
- Wall-hung near tank, or
- above the tank in closet

Mininum 24" of clearance is required in front of pod for wiring installation and future service access.
Mount to studs or sturdy surface with screws using provided mounting holes.

The pod will require a 120V power outlet for the included 24 VDC power supply (refer to SANCO2 Low Voltage Wiring).
The Harvest Pod will require either an Ethernet or WiFi connection. This enables over-the-air updates, access to weather forecasts, and remote monitoring of the system. Ethernet is the most robust and therefore recommended option. See Start Up for more info.

| Size |
---|---|
A: Heat Pump Cold | 1/2" NPT |
B: Utility In | 3/4" NPT |
C: DHW Hot | 3/4" NPT |
D: Air Handler Supply | 1/2" NPT |
E: Air Handler Return | 1/2" NPT |
F: Cold Water to Tank | 3/4" NPT |
G: Hot from Tank | 3/4" NPT |
H: AHU Return to Tank | 1/2" NPT |