Installation Manual
Components

Tank

 WARNING: Installation instructions in this manual are not meant to encompass 100% of SANC02 installation guidelines and requirements. Refer to the manufacturer for complete instructions.

Location

The tank can be located no further than 66ft (20m) from the SANCO2 heat pump, and no more than 27ft (7m) below it.

Tank must be installed in an area not subjected directly to outside weather.

Dimensions

Source: SANCO2 GS4 Installation Manual
Source: SANCO2 GS4 Installation Manual


Dimension

83 Gal

119 Gal

A: Height

68-7/8"

63-3/8"

B: Hot Water Outlet and PRV

60-1/4"

56"

C: Heat Pump Return

60-1/4"

60-1/4"

D: Sensor Port

40-5/8"

56"

E: Hydronic Return & Cold Water to HP

8-3/4"

4"

F: Diameter

24-1/2"

28"

Dry Weight

115 lbs

345 lbs

 NOTE: Allow space between the tank and the wall for tank insulation to be added later.

Mounting

The tank is a passive storage vessel (no internal heating element). Therefore, there is no required:

  • Pedestal
  • Flue, or
  • Condensing section

 NOTE: Min. 1" high-density insulation below the tank is required (see Insulation section) for good system performance

 NOTE: It is required to wrap R6, or greater, insulation (see Insulation section) around the tank. It is easiest to do this prior to plumbing it.

 WARNING: Follow all local jurisdiction codes for bracing of tank

Plumbing Connections

Document image




83 Gal

119 Gal

F: Air Handler Return

3/4" NPT

1-1/2" NPT

G: Hot Water Outlet

3/4" NPT

1-1/2" NPT

HPH: Hot Water Return from HP

3/4" NPT

3/4" NPT

H: Cold Water Inlet/Return to Heat Pump

3/4" NPT

3/4" NPT

PRV: Pressure Relief Valve

Valve Provided

Valve Provided

 NOTE: Dielectric unions or 6" brass couplings are required at all 119 Gal tank connections. Heat Traps (see Plumbing System Diagram) required for top connections.