Single HPWH Setup
Location
The Heat Pump Water Heater (HPWH) should:
- Be located no further than 66ft (20m) from the tank, and no more than 23ft (7m) above it. Additionally, minimizing pipe length to the tank/pod maximizes efficiency
- Maximum 6 bends, use long-radius elbows, not “street Ls”
- Be installed outside, with adequate ventilation (see Required Unit Clearances)
- Be installed in such a way where water can drain without damaging the heat pump
The heat pump can be installed either on a:
- Preferably a pad or other firm base, or
- On wall-mounted brackets.
Dimensions

Required Unit Clearances

Allow 4” of clearance below the heat pump for the drain plug.
Installation Example and Additional Dimensions

Powering the HPWH
Electrical Requirements:
| Power Supply: | 240V-1Ph-60Hz |
|---|---|
| Breaker Size: | 15A |
| MCA: | 7.2A |
A quick disconnect must be installed adjacent to heat pump in accordance to NEC and local codes
Main Power Connection

Refer to Wiring for low voltage wiring.
Plumbing Connections