Insulation

Pipes

  • All pipes, excluding the Cold Supply pipe (line B), are required to be insulated with minimum 1” (R-6) insulation.
  • Include insulation on all valves and couplings.
  • Pipes should be clamped outside of the insulation.

CO2 Heat Pump Water Heater

  • All requirements above apply to CO2 HPWH piping.
  • Piping inside of CO2 HPWH cover should also be insulated.
  • Ensure all outside piping is weatherized.

SANCO2 Tank

  • 1+” polyiso (min. R-6) insulation required under tank
  • Insulate tank with min. R-8 insulation around sides and top of tank.
  • Insulate pressure relief valve with min. R-6 insulation.

Reclaim Tank

  • No additional insulation is needed under, or around, the Reclaim tank
  • Place included fiberglass insulation between and around the top plumbing connections. Attach lid using the four screws provided. (See image below)
  • Use the provided K-flex insulation on the provided heat traps.
  • Install the provided PRV insulation, and insulate at least 6” along the discharge plumbing.
Reclaim tank insulation